Proportional pressure, measured - control mode

Constant speed pump1: Constant speed pump
Constant speed pump1: Constant speed pump
Diff. pressure controlled2: Diff. pressure controlled
Diff. pressure controlled2: Diff. pressure controlled

Proportional pressure is used in circulation systems with an exten­sive pipe system and control valves to generate a variable flow.

Proportional pressure is mostly used in circulation systems with an exten¬sive pipe system and control valves to generate a variable flow.
The pressure loss in the control valves is lower than 50% of the total pressure loss. The differential pressure sensor should be placed at the farthest consumer.

  • Heating systems with 2-way valves
  • District heating net
  • Air-con system with 2-way valves